AC Current transducer AP-B10
IPN = 10 .. 400 A
Split-core transducer for the electronic measurement AC sinusoidal
waveform currents, with galvanic isolation between the primary circuit
(high power) and the secondary circuit (electronics). Switch selectable
measuring ranges and RMS 0-5V and 0-10V switch selectable voltage
output.
Electrical data
Primary Nominal Current
IPN (A.t.rms)
10,25,50
50,75,100
100,150,200
200,300,400
RL
VC
IC
VSL
VSL
ÎP
Output Voltage (Analog)
VOUT (V DC)
0-5
0-5
0-5
0-5
or
or
or
or
0-10
0-10
0-10
0-10
Type
AP
AP
AP
AP
Load resistance
Supply voltage
Current Consumption
Output voltage limitation (0-10V)
Output voltage limitation (0-5V)
Overload capability
50 B10
100 B10
200 B10
400 B10
RoHS since
date code
46320
46333
47282
planned
≥ 10
kΩ
+ 24 ± 5%V DC
< 30
mA
14
V
7
V
no limitation
Accuracy-Dynamic performance data
X
ε
L
VOE
TCVOE
TCVOUT
tr
BW
Accuracy @ IPN, TA = 25°C (excluding offset)
Linearity error (0 .. ± IPN)
Electrical offset voltage @ TA = 25°C
Temperature coefficient of VOE
Temperature coefficient of VOUT (% of reading)
Response time to 90% of IPN step
Frequency bandwidth (± 1 %)
< ± 1 % of IPN
< ± 0.5 % of IPN
< ± 0.5 % of IPN
±1
mV/K
± 0.1
%/K
< 150
ms
30 .. 2000 Hz
General data
TA
TS
m
IPxx
Ambient operating temperature
Ambient storage temperature
Mass
Protection degree
- 20 .. + 60
- 20 .. + 85
90
IP20
°C
°C
g
Features
• RMS output (average)
• Split-core type
• 0-5 VDC and 0-10 VDC switch
selectable voltage output
• DIN rail or Panel mounting
• Switch selectable measuring ranges
• Isolated plastic case recognized
according to UL94-V0.
Advantages
• Large aperture for cable up to
Ø18mm
• High isolation between primary and
secondary circuits
• Eliminates insertion loss
• Easy installation
Applications
• Automation systems
Analog current reading for remote
monitoring (e.g. motor) and
software alarms.
• Panel meters
Simple connection to power
consumption displays.
Application domain
• Energy and Automation
Page 1/4
080212/5
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Current Transducer AP-B10
Isolation characteristics
Vb
Rated isolation voltage rms 1)
300
with IEC 61010-1 standards and following conditions :
- Reinforced isolation
- Over voltage category CAT III
- Pollution degree PD2
- Heterogeneous field
Rms voltage for AC isolation test 2), 50 Hz, 1min
5
Partial discharge extinction voltage rms @ 10 pC
1.5
Impulse withstand voltage 1.2/50 µs
6.1
Creepage distance
5.5
Clearance distance
5.5
Comparative tracking index (Group I)
600
Vd
Ve
Vw
dCp
dCl
CTI
V
kV
kV
kV
mm
mm
Notes : 1) If insulated cable is used for the primary circuit, the voltage category could
be improved according to the insulation characteristics given by the cable
manufacturer.
e.g.
Cable insulation (primary)
Category
HAR 05
600V CAT III
HAR 07
1000V CAT III
2)
Between primary (completely filling the aperture) and secondary.
Page 2/4
080212/5
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Current Transducer AP-B10
Safety and warning notes
In order to guarantee safe operation of the transducer and to be able to make proper use of all features and functions,
please read these instructions thoroughly!
Safe operation can only be guaranteed if the transducer is used for the purpose it has been designed for and within
the limits of the technical specifications.
Ensure you get up-to-date technical information that can be found in the latest associated datasheet under www.lem.com.
Caution! Risk of danger
Ignoring the warnings can lead to serious injury and/or cause damage!
The electric measuring transducer may only be installed and put into operation by qualified personnel that
have received an appropriate training.
The corresponding national regulations shall be observed during installation and operation of the transducer
and any electrical conductor.
The transducer shall be used in electric/electronic equipment with respect to applicable standards and safety
requirements and in accordance with all the related systems and components manufacturers’ operating
instructions.
Caution! Risk of electrical shock
When operating the transducer, certain parts of the module may carry hazardous live voltage (e.g.
primary conductor, power supply).
The user shall ensure to take all measures necessary to protect against electrical shock.
The transducer is a built-in device containing conducting parts that shall not be accessible after installation.
A protective enclosure or additional insulation barrier may be necessary.
The transducer shall not be put into operation if the jaw opening is open (split core version) or the installation
is not completed.
Installation and maintenance shall be done with the main power supply disconnected except if there are no
hazardous live parts in or in close proximity to the system and if the applicable national regulations are fully
observed.
Safe and trouble-free operation of this transducer can only be guaranteed if transport, storage and installation are carried
out correctly and operation and maintenance are carried out with care.
Page 3/4
080212/5
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Dimensions AP(R)-B10 (unit : mm, 1mm = 0.0394 inch)
Output Vo ltage
Selection Switch
Front Vie w
Left View
55
16.40
DIN size35.50
69
14.80
Rang e Selection Switch
4.7 0
20
40(distance between screws)
21
33.50
37
Axis of ape rture
25
18 .50
67
Plug-in connector included : XW4B-03C1-H1 (OMRON)
18.50
Bottom View
0-5, 10V Selectable
Connections
GND
• Wires up to ∅ 2 mm
RL
OUTPUT
AP/APR
+24VDC
• Female connector provided (spring terminal blocks)
• User-friendly spring-cage connection for no-tool direct
conductor connection
Output
Connector
3(-) 2(out)1(+)
Output Switch
Mechanical characteristics
Range Switch
Front
+24VDC
Is
• General tolerance
• Primary aperture
± 1 mm
∅ 18.5 mm
• Panel mounting
• Distance between holes
2 holes ∅ 4.0 mm
40.0 mm
For panel mounting, replace M4 screws by new one (not
supplied) with appropriate length to panel´s thickness.
OUT
Ip
GND
Page 4/4
080212/5
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com